Details
DIESEL GENERATOR ESE 8000 SK-ED
♦ Power (kVA) standby (ESP) / prime (PRP) - 8,0 / 7,2
♦ Power (kW) standby (ESP) / prime (PRP) - 7,2 / 6,4
♦ Speed (rpm) - 3000
♦ Standard voltage (V) - 230
♦ Power factor (cos phi) - 0,9
♦ Amperage (Amp) - 31
STANDARD FEATURES
♦ Command & control panel with measurement & metal control devices
♦ 400 V/ 230 V sockets (as the case)
♦ Dynamic battery charging alternator
♦ Oversized startup battery
♦ Emergency stop button
♦ Fuel tank sized for long autonomy
♦ Vibration dampers
♦ Electrical lines protected with tubing & seals
♦ Exhaust muffer
♦ Magnetothermal and short-circuit protection
♦ Mounting / dismantling access panels
♦ Crane or forklift handling system
♦ Flameproof and antiphonic insulation
DIESEL ENGINE
Producator - KOHLER
Model - KD 440
Capacitate cilindrica (l) - 0,442 - 1 cylinder
Putere HP - 10,5 la 3000 rpm
Fuel - Diesel
Authonomy at 75% load - aprox. 10 h
Fuel consumption at 75% load (l/h) - 1,9
Start - Electrical
Optional - Automatic start with ATS
ALTERNATOR
Model - Linz E1C10M
Voltage - 230 V
Frequency - 50 Hz
Nominal power (kVA) - 8,0
Excitation type - Self-excited
Adjustment type - AVR
Power factor - 0,9
Protection - IP23
CONTROL PANEL
1. Multipurpose plug automatic conection
2. Single-phase socket 230V/16A
3. Single-phase socket 230V/32A
4. Voltmeter
5. Hour meter running
6. Contact key
7. Cold start electric shock
8. Grounding socket
♦ Standard automatic control panel with ATS included (optional):
The command and control panel is mounted inside the casing, in a metal box with IP 54, equipped with:
- ComAp AMF 9 command module
- Static battery charger
- Emergency stop button & circuit breaker fuses
- Overcurrent differential protection
- Protection relays
- Generator contactor
- Network contactor
- Measuring transformers
Configuration:
1. ComAp AMF 9 command module
2. Lock panel
3. On / Off button
4. Emergency button
5. IP55 control box
♦ Command module standard specifications:
- Microprocessor control
- 132 x 64 pixel LCD display
- Programming on front panel as well as through PC software
- Control buttons and soft touch navigation
- Remote communication via USB or with optional modules via RS232, RS485, Ethernet or SMS
- Store 350 events with date and time
- Maintenance programming 3 levels
- Engine heater control - Optional
Display:
Engine - engine speed; oil pressure; coolant temperature; running time; battery voltage; maintenance data.
Alternator - voltage (L – L, L – N); current (L1 – L2 – L3); frequency; kW; Pf; kVAr, kWH, kVAh, kVArh; phase sequence.
Main network - voltage (L – L, L – N); frequency, mains ready; mains off; generator set ready, generator set disconnected, active power kW, apparent power kVA, reactive power kVA r, power factor, phase sequence.
Warning - battery faulty charging, low battery voltage, fail to stop, low fuel level, overload, phase reversing, speed sensor failure.
Alarms - low oil pressure, high engine temperature, under / over voltage, under / overfrequency, under / overvoltage, ECU fault -optional.
Status display - missed start, emergency stop, low oil pressure, high engine temperature, under / overspeed, under / overfrequency, under / overvoltage, oil sensor, phase rotation, overload, overcurrent group, phase reversal.
♦ Static battery charger: Made with TSD technology, with high efficiency. Protected for shortcircuit currents, it can be used as a current source, input voltage 196-264 V, output voltage 27.6 V / 5A or 13.8 V / 5A.
♦ Standards:
Electrical safety / EMC, BS EN 60950; BS EN 60950 – 6 – 2 EMC; BS EN 61000 – 6 – 4 EMC.
HOUSING
Made of galvanized steel, painted in electrostatic field, soundproofed. The carcasses are designed to optimize the cooling of the engine and alternator assembly, and can be mounted outdoors, providing protection against weathering and low noise levels.
1. Mobile access cover
2. Stainless steel locks
3. Single Phase socket
4. Multipurpose plug automatic conection
5. Air intake grilles
6. Flexible pads
7. Residential exhaust tube
8. Air exhaust fans
9. Information tool
DIMENSIONS & WEIGHT
Closed generator sizes & weight |
|
Sizes (length x width x height) (mm) |
1200 x 700 x 1070 |
Weight (kg) |
130 |
Fuel tank capacity (liters) |
20 |
Noise level @ 7m |
68 |
OPTIONAL FEATURES
♦ Electrical panel anti-condensation heating system
♦ Fuel heating system
♦ Preheating system for canopy
♦ Automatic control panel with included ATS transfer panel
♦ Bypass panel - ENDRESS palented invention – OSIM patent 00010 / 2012
♦ Trailer
♦ Start by remote control
♦ Groundless protection
♦ Liquid retention tray
♦ Liquid leakage detection sensor
Optional: RAR homologated auto trailer
Endress Group Romania S.R.L. certifications:
ISO 9001 : 2008, ISO 14001 : 2005, ISO 18001 : 2008.
ZENESSIS generators are CE compliant, and are tested according to the EU legislation on noise levels 2000 / 14 / EC.
Reference ambient conditions: 1000 mbar; 25° C; 30% relative humidity; power according to ISO 3046 / ISO 8528 standards
Prime power (PRP) – ISO 8528
Prime power (PRP) - represents the continuous power a generator is able to provide continuously while supplying a variable electrical load when operating for an unlimited number of hours per year, under the agreed operating conditions, maintenance intervals and procedures being performed as prescribed by the manufacturer.
Standby power (ESP) – ISO 8528
Standby power (ESP) is the maximum power available at a variable load, under the operating conditions provided, that a generator is able to provide in case of power failure or under test conditions, maintenance intervals and procedures being performed as prescribed by the manufacturer.
Additional Information
Producator | KOHLER |
---|---|
Fuel | DIESEL |