Details
ZMZ 80K
Specifications
Model: ZMZ 80K
Power: 80 kW / 80 kVA
No of phases IN : OUT - 3:3
Input
Nominal Voltage: 380 / 400 / 415 VAC
Voltage range: 172÷287 Vac (L-N) / 300÷500 Vac (L-L) @ 100% sarc.
92÷287 Vac (L-N) / 160÷500 Vac (L-L) @ sarc. liniara
Frequency: 50 / 60 Hz
Frequency range: -20% ÷ +20%
THDi: <3%
Input power factor: >0,99
Output
Nominal voltage: 380 / 400 /415 VAC
Power factor: 1,0
Static / dynamic voltage regulation: ±1% / ±3%
Nominal frequency: 50 / 60 Hz ± 0,01 Hz
Inverter overload resistance: 105% - cont.; 115% - 60 min., 130% - 10 min., 150% - 60 sek., >151% - 0,2 sek.
Efficiency in On-Line mode: >96%
Efficiency in Eco mode: 99%
Crest factor: 3:1
Battery
Type: Sealed maintenance-free VRLA
No. of batteries in string: Configurable: 30 ÷ 40 psc
Charging time: 3 - 8 hours to 90% capacity (configurable)
Maximum charging current: 20 A
Charging cycle: According to DIN 41773 with automatic shutdown of charging according to the criterion of current and voltage, with time control.
Bypass
Automatic bypass: Static switch type Bypass, uninterruptible changeover
Bypass manual mechanical: Standard
Dimensions and weight
Dimensions and weight UPS (W x D x H): 450 x 840 x 1400 mm / 210 kg
Signaling and communication ports
Work status indicator: 4.3 "touch display, LED indicators, audible alarm
Standard communication: 3 x Smart Slot for additional communication cards
2 x REPO (NO/NC), 3 x Dry Contact Out, RS485, Modbus
Environmental conditions
Noise level: <60 dB
Permissible operating temperature: 0°C ÷ 40°C
Recommended working temperature: 15°C ÷ 25°C
Storage temperature: -25°C ÷ 55°C
Humidity: 0 ÷ 95% (without condensation)
Standards
Resistance to interference: EN 62040-2:2005, EN 62040-2:2006
Safety: IEC62040-1-1, CE
Optional equipment
- SNMP card
- Batteries in rack or in battery modules
- RS 232
- Sensor for battery voltage compensation
- Uninterruptible Bypass External
- Remote signaling panel
- Additional Dry Contact card
Additional Information
Input voltage | 380/400/415 VAC |
---|---|
Input frequency | 50/60 Hz |
Operating temperature for UPS | 0°C ÷ 40°C |
Power (kVA) | 80 |