ZRM 3

Additional Information

Input frequency 50/60 Hz
Power (VA / W) 3000 / 2700
Operating temperature for UPS 0°C ÷ 40°C
Input power factor >0,99

Quick Overview

ZRM 1-10kVA Series

Details

  ZRM 3

                                                  Specifications                                                

     Model:   ZRM 3

     Power:   3000 VA / 2700 W

     No of phases IN : OUT  -  1:1

     Input

     Nominal Voltage:   208 / 220 / 230 / 240 VAC

     Voltage range:   -30% ÷ +30% @ 100% ≥ load. ≥ 80% 

                                -40% ÷ +30% @ 80% ≥ load. ≥ 70%

                                -48% ÷ +30% @ 70% ≥ load. ≥ 60%

                                -52% ÷ +30% @ 60% ≥ load. ≥ 0%

     Frequency:   50/60 Hz

     Frequency range:   -20% ÷ +20%

     THDi:   <3%

     Input power factor:   ≥0,99

     Output

     Nominal voltage:   208/220/230/240 VAC

     Power factor:   0,9

     Static / dynamic voltage regulation:   ±1% / ±3%

     Nominal frequency:   50/60 Hz ±0,05 Hz

     Inverter overload resistance:   110% - fara limita, 130% - 5 min., 140% - 30 sec., >140% -1,5 sec.

     Efficiency in On-line mode:   >92%

     Efficiency in Eco mode:   99%

     Controlled socket groups - with programmable power off:   1 x 4 pcs

     Type and  number of sockets:   IEC320-C13 x 8

     Terminal board:   n/a (Plug&Play)

     Crest factor:   3:1

     Batteries

     Amount of internal batteries:   4 x 7/9 Ah

     Cold start:  Yes

     Connector for external batteries:   Yes

     Charging time:   4 hours up to 90% of capacity (configurable)

     Dimensions and weights

     Dimensions and weight of UPS (W x D x H):   438 x 510 x 88 (2U); 19.5 kg

     Dimensions and weight of battery module (W x D x H):   438 x 510 x 88 (2U); 24 kg

     Communications

     Working indicator:   LCD + indicators LED, alarm sound alarm

     Communications:   Standard: USB, RS232, TVSS, Smart slot, REPO

                                    Options: Dry Contact, SNMP card

     Environmental

     Noise level:   <45 dB

     Operating temperature for UPS:   0°C ÷ 40°C

     Recommended operating temperature for UPS:   15°C ÷ 25°C

     Storage temperature:   -25°C ÷ 55°C

     Humidity:   0 ÷ 95% (without condensation)

     Standards

     Resistance to interference:   EN 62040-2:2005, EN 62040-2:2006

     Safety:   IEC62040-1-1, CE, 62040-3 :2001

 

                                   Optional equipment                                 

     - SNMP cards

     - Dry contact (A5-400)

     - Environmental sensor (EMD) 

     - Additional battery module

     - Maintenance bypass

     - Rail kits 19"

     - EPO

Additional Information

Input frequency 50/60 Hz
Power (VA / W) 3000 / 2700
Operating temperature for UPS 0°C ÷ 40°C
Input power factor >0,99